A substation automation system has to do more than move measurements to a control room. It must connect field equipment, protection devices, monitoring systems and operator workstations while keeping their communications reliable and their records aligned in time. If a switch or link fails, operators still need visibility into the station, and protection-related messages must continue to reach the devices that depend on them.
The network is easier to understand as three cooperating layers: the process layer, where electrical equipment is measured and controlled; the bay layer, where protection and control functions operate; and the station control layer, where information is monitored and managed. Industrial Ethernet switches connect these layers, but reliable operation depends on more than switch capacity. Network separation, redundant paths, communication protocols and time synchronization all have distinct roles.
Three layers, three different communication needs
At the process layer, merging units and intelligent terminals connect with equipment such as electronic current transformers and primary switches. A merging unit handles measurement data from field equipment, while an intelligent terminal supports interaction with that equipment. Process-layer switches carry the resulting communications across the station’s process network.
The bay layer contains devices associated with individual circuits and protection functions: measurement and control units, transformer and line protection, busbar protection, automatic transfer equipment, metering devices and disturbance recorders. This is where data from the field becomes useful for protection, control and event analysis.
At the station control layer, hosts, operator workstations, remote communication devices and other management equipment provide a station-wide view. Station-control switches connect these systems over the station network. Keeping the three layers distinct helps engineers expand or maintain one part of the system without treating every device as though it has the same communication requirements.
IEC 61850, also known in China as DL/T 860, provides a common framework for communication between substation devices. Its message types serve different purposes:
- MMS carries monitoring and control information used at the station-control level.
- GOOSE carries fast event and control messages, including those used in protection coordination.
- SV, or sampled values, carries measurement samples used in process-layer communication.
These are different kinds of traffic, not interchangeable names for an Ethernet connection. A network design must account for where each message travels and what happens if its path is interrupted.
Why two networks are better than one path
In a dual-network design, station-control and process-layer communications can each use separate A and B networks. If one network path is affected by a fault, the other provides a redundant route. Station-control and process networks are also independently organized, so their different traffic and operating requirements can be addressed separately.
Redundancy can additionally be built into a network topology. Ring networks provide alternative routes around a failed link, while technologies such as RSTP, PRP and HSR address fault recovery or redundant communication in different ways. A redundant cable layout alone does not establish a particular recovery time: the behavior depends on the network technology, device support and actual configuration. Protection-related traffic therefore deserves particular attention when choosing and testing a topology.
Switches are the communication points that make this design practical. In Wintop’s substation automation architecture, the YT-CM6028-Z-E24G4 is applied at the station-control layer. The YT-CM6016-G-G16 and YT-CM6020-G-F16G4 are used for process-layer networking. Model choice should follow the required network layout, connected equipment and applicable product specifications rather than the three-layer diagram alone.
A substation is also a demanding place for communication equipment. Industrial-grade wide-temperature operation and electromagnetic compatibility, or EMC, design address the temperature variation and strong electromagnetic interference found in this environment. The objective is stable, continuous communication during long-term, 7 × 24-hour operation.
Time synchronization makes events understandable
Reliable delivery answers whether data arrives. Time synchronization answers when an event happened. That distinction matters when protection devices, measurement systems and disturbance recorders produce separate records of the same incident.
A station can use GPS or BeiDou as a common time source and distribute timing through methods including SNTP and IRIG-B. SNTP supports millisecond-level synchronization at the station-control layer. The process layer has a more demanding microsecond-level synchronization requirement. A microsecond is one-millionth of a second; a millisecond is one-thousandth. The difference is significant when measurement samples and protection-related events from different devices must be aligned.
Using one time reference across the station helps operators interpret alarms and recorded events in sequence. It also supports coordination among protection, measurement, metering and recording systems. Time synchronization does not replace a reliable network, but without it, correctly delivered records can still be difficult to compare.
What changes when a station grows or is upgraded?
A new substation and an automation retrofit may use the same three-layer principle, but they do not necessarily have the same integration problem. An existing station may need to accommodate protection and control devices from different manufacturers, as well as protocol conversion equipment. Open interconnection and compatibility with relevant industrial protocols help bring those devices into a coherent monitoring and communication system.
The layered approach also gives expansion a clear place in the architecture. Field devices belong at the process layer; protection and measurement functions belong at the bay layer; station-wide monitoring belongs at the station-control layer. As devices are added, engineers can assess their traffic, timing and redundancy needs at the appropriate layer instead of extending a single undifferentiated network.
Wintop’s industrial switches have been applied in substation projects including 110 kV, 220 kV and 500 kV transmission and transformation projects in the Shenzhen area, as well as projects in Yunnan, Xinjiang, Tibet and Inner Mongolia. These applications illustrate the role of industrial switching in connecting station monitoring with process-layer and protection-related equipment. The underlying design questions remain the same across projects: which devices need to communicate, how quickly must messages arrive, what happens after a fault, and how will events be timestamped?
A dependable substation automation network is therefore not defined by any single protocol or switch. It comes from matching the three-layer architecture to the station’s devices, giving critical communications redundant paths, and keeping time consistent across the system. Those choices turn separate measurements, protection actions and operator displays into a coordinated view of the substation.