A substation automation network has to carry several kinds of information at once. Operators need a current view of equipment status, protection devices need to exchange time sensitive signals, and measuring devices need a consistent record of when events occurred. Connecting every device is therefore only part of the job. The network must also keep those exchanges organized and available when a link fails.
A useful way to understand the design is to follow data from field equipment to the control room. In a typical three layer architecture, the process layer gathers measurements and interacts with primary equipment, the bay layer handles protection and control for individual parts of the substation, and the station control layer brings information together for monitoring and management. Wintop applies this structure in substation automation networks with separate redundant networks and a common approach to time synchronization.
How the three layers work together
At the process layer, electronic current transformers, merging units and intelligent terminals connect the physical substation to its communication network. A merging unit prepares measured values for transmission; an intelligent terminal supports the exchange of information with equipment such as primary switches. Process layer A and B networks provide separate communication paths for these field devices.
The bay layer contains devices such as transformer, line and busbar protection relays, measurement and control units, meters, disturbance recorders and protocol converters. A protection relay acts on conditions within its assigned part of the substation, while a disturbance recorder preserves information that helps operators examine an event afterward. Keeping these functions at the bay layer makes their relationship to the field equipment clear.
At the station control layer, hosts, operator workstations, remote communication devices and other management equipment support supervision of the whole station. Station control A and B networks connect these systems to the equipment below. The layers have distinct roles, but their value comes from coordinated operation: a field measurement can reach a protection device, while its status and event information can also reach an operator.
Why separate networks and protocols matter
IEC 61850, also known in this context as DL/T 860, provides a common framework for communication among substation devices. Three types of traffic are especially relevant:
- MMS carries information used for station level monitoring and control.
- GOOSE carries fast event and control messages, including signals used in protection coordination.
- SV, or sampled values, carries digitized measurement samples.
These messages serve different purposes and place different demands on the network. A station automation design therefore considers where traffic originates, where it must go and how a fault in one communication path affects the devices that depend on it.
Wintop’s substation architecture uses separate station control and process layer networks, with A and B networks providing redundant paths at each level. Ring redundancy can also be used where the topology calls for it. Technologies such as RSTP, PRP and HSR are options for fault recovery or redundant communication, but their behavior depends on the chosen topology and the capabilities of the connected devices. A switch model and a network design should be evaluated together rather than treating a protocol name as a guarantee of a particular recovery time.
For example, Wintop identifies YT-CM6028-Z-E24G4 for station control network communication. YT-CM6016-G-G16 and YT-CM6020-G-F16G4 are process layer switch options. Their roles differ because station control traffic and process layer exchanges are placed on different networks; the appropriate configuration depends on the devices, links and redundancy method required by the project.
Time synchronization gives events a usable sequence
Reliable communication does not, by itself, give operators a reliable event timeline. If protection devices, merging units and monitoring systems use inconsistent clocks, records from the same disturbance become harder to align.
Substation designs address this with a common time source, such as GPS or BeiDou, distributed through suitable synchronization methods. In the described architecture, station control systems support SNTP for millisecond level synchronization, while process layer applications call for microsecond level precision and may use IRIG-B timing. A millisecond is one thousandth of a second; a microsecond is one millionth. The tighter process layer requirement reflects the need to relate measurements and events precisely across devices.
Those figures describe synchronization requirements at different layers, not an automatic result from installing a clock. The time source, distribution method and receiving devices all have to support the precision the application needs.
What changes when the same network ideas move to other power facilities?
Layering and redundancy are useful beyond substations, but the equipment being connected changes the design. In an energy storage station, the network may bring together storage cabinets, power conversion systems (PCS), battery management systems (BMS) and monitoring servers. Wintop’s storage monitoring architecture separates device access, network aggregation and central applications, with independent A and B networks for MMS and GOOSE traffic. For key telemetry, a typical refresh target is three seconds or less; telemetry here means measured operating data reported to the monitoring system.
Wind and solar sites present another challenge: field devices are spread across a wider area. Wintop’s wind monitoring design uses industrial switches, including RS6010-2GF8T, RS205-1F4T and RS203-1F2T, to connect equipment at turbines, towers and box transformers. RS6010 series switches can form a WR-ring gigabit ring for redundant transmission toward the monitoring center. A solar site can instead use a 100 Mbit/s fiber ring between collection nodes that gather data from inverters, combiner boxes, meters and environmental monitoring devices. In each case, the network structure follows the location of the equipment and the information the control center needs.
Real deployments illustrate the range of these applications. Wintop industrial switches have been used in substation projects at 110 kV, 220 kV and 500 kV, as well as in energy storage and renewable energy monitoring projects. The voltage rating describes the substation project, not a performance rating of the switch.
The central question in substation automation is whether measurements, protection messages, operator information and event times can remain coherent across the entire station. A three layer architecture gives each device a defined place; redundant networks provide alternate communication paths; and coordinated timing makes records from different devices meaningful together. Those are the relationships to examine when designing or upgrading a substation network, alongside the specific switch, protocol and timing requirements of the equipment it connects.